Electric Motors Failures

Electric Motors Failures

Sunday, August 7, 2022 Motor failures VFD VSD Bearing Current EDM

(37% of are connected to drives, account for 82% of Winding defects)

Implement Electrical Maintenance Programmes for the industry which include conducting Motor Circuit Analysis.

This testing program forms a database of tests from many sectors and over a range of Low Voltage Motor sizes.

I will reference 1983 Electric Power Research Institute (EPRI) project performed by General Electric (GE) [1] where 4797 motors were evaluated with 1227 failures. The title “Large Electric Motor Reliability” I’m not sure what Large is?

Here’s a Snapshot of that Study

First it was noted that more than 90% of the failures occurred in 54% of the facilities evaluated, and half of the failures occurred in 17% of the facilities.”

The average failure rate of motors across all the facilities was 3.4% per unit annually, with some operations having a higher rate, and 46% of them having very low failure rates.

In all, the study found that those plants at the extremes had a failure rate of 9.3% per year (17% of facilities) and 13% of the sites had about a 0.8% failure rate.”

So whats this telling you, Some Facilities have Motor Reliability others don’t. The range is more than 12 times the failure rate between sites.

Motor Bearings 41% are the biggest issue, closely followed by Motor Winding at 37% of defects.

A dairy company in Australia with over 3500 rotating machines on the Vibration Analysis database had initial defects of 12% of Assets, and when Motor Circuit Analysis was conducted 8% of tested assets had defects. So this ratio is quite valid.

This data dating 1983 is quite old and in my view one thing that has changed dramatically, is the use of Variable Speed Drives. In 1983 (nearly forty years ago) drives weren’t yet to be commercialized.

So what does 3Phi Reliability data look like in 2022?

Keep in mind this data is not failures but detected defects before failure.

17% Stator Winding (Phase Angle,Current Frequency Response ALL Test Pro )

22% Resistive Defects (Imbalances greater than 3%)

2.3% Insulation Resistance Defects (Lower than 100 Mega Ohm)

Total 41.3% which up from the above study 1983 at 37% but close.

This is the interesting part of the data

Totaling up the Assets 63.2% were started Direct on Line, Star Delta or Soft Starter.

36.8% were connected to a Variable Speed Drive.

Of the Motors with significant Winding defects 82% were connected to a variable speed drive. So 37% of the assets (Drives) accounted for 82% of the Winding defects.

Summary

To date much focus has been on bearing currents emitted from Drives, but these numbers suggest Insulation & Windings defects suffer significant consequences of this failure mode.

Ensuring proper grounding of Variable Speed Drives is the first step, followed by Drive Emission testing at the Motor.

The above study indicates good Electrical Preventative Maintenance can have a 12 times reduction in “Median Hours Downtime per Failure”

Mark Gurney -Motor Analyst

3Phi Reliability SARL.

Francky
wrote
Monday, July 24, 2023, 06:05
Thank you for this informative article on Electric Motor

Blog  Free Advice on Electric Motor Reliability and Energy Savings


Feel free to Copy Link and use on your Website  (Blue Chain Button)- MENU ABOVE
3Phi Reliability strive to provide interesting and informative topics to clients to Gain Electric Motor Reliability and Return Energy Savings

Gain Electric Motor Reliability & Return Energy Savings

Most of clients make gains on the every first day of implementation. Best Practice Motor Management has a short Return on Investment, improving Electric Motor Reliability and Energy Savings are immediate.
Search